Description:
MDR-20 is a slim line DIN rail Class I switching power supply.Designed with a fully isolated plastic case to prevent user contact and the risk of shock.Featuring up to 88% efficiency this series can be cooled using only free air convection up to 60°C which significantly increases the reliability and lifetime of the power supply.Other standard features include its low no-load power consumption, to save energy, short circuit, overload, and over voltage protections, and DC OK relay contact with LED indicator for monitoring the PSU status.
MODEL | MDR-20-5 | MDR-20-12 | MDR-20-15 | MDR-20-24 | |
DC VOLTAGE | 5V | 12V | 15V | 24V | |
RATED CURRENT | 3A | 1.67A | 1.34A | 1A | |
CURRENT RANGE | 0 ~ 3A | 0 ~ 1.67A | 0 ~ 1.34A | 0 ~ 1A | |
RATED POWER | 15W | 20W | 20W | 24W | |
RIPPLE & NOISE (max.) Note.2 | 80mVp-p | 120mVp-p | 120mVp-p | 150mVp-p | |
OUTPUT | VOLTAGE ADJ. RANGE | 4.75 ~ 5.5V | 10.8 ~ 13.2V | 13.5 ~ 16.5V | 21.6 ~ 26.4V |
VOLTAGE TOLERANCE Note.3 | ±2.0% | ±1.0% | ± 1.0% | ± 1.0% | |
LINE REGULATION | ±1.0% | ±1.0% | ±1.0% | ±1.0% | |
LOAD REGULATION | ±1.0% | ±1.0% | ± 1.0% | ± 1.0% | |
SETUP, RISE TIME Note.5 | 500ms, 30ms/230VAC 1000ms, 30ms/115VAC at full load | ||||
HOLD UPTIME (Typ.) | 50ms/230VAC 20ms/115VAC at full load | ||||
VOLTAGE RANGE | 85 ~ 264VAC 120 ~ 370VDC | ||||
FREQUENCY RANGE | 47 ~63Hz | ||||
INPUT | EFFICIENCY (Typ.) | 76% | 80% | 81% | 84% |
AC CURRENT (Typ.) | 0.55A/115VAC 0.35A/230VAC | ||||
INRUSH CURRENT (Typ.) | COLD START 20A/115VAC,40A/230VAC | ||||
LEAKAGE CURRENT | <1mA/240VAC | ||||
OVERLOAD | 105 ~ 160% rated output power | ||||
PROTECTION | Protection type: Constant current limiting, recovers automatically after fault condition is removed | ||||
OVER VOLTAGE | 5.75 ~ 6.75V | 13.8 ~ 16.2V | 17.25 ~ 20.25V | 27.6 ~ 32.4V | |
Protection type: Shut down o/p voltage, re-power on to recover | |||||
FUNCTION | DC OK ACTIVE SIGNAL (max.) | 3.75 ~ 6V / 50mA | 9 ~ 13.5V / 40mA | 11.5 ~ 16.5V / 40mA | 18 ~ 27V / 20mA |
WORKING TEMP. | -20 ~ +70C (Refer to “Derating Curve”) | ||||
WORKING HUMIDITY | 20 ~ 90% RH non-condensing | ||||
ENVIRONMENT | STORAGE TEMP., HUMIDITY | -40 ~ +85C, 10 ~ 95% RH | |||
TEMP. COEFFICIENT | ±0.03%/C (0 ~ 50C) | ||||
VIBRATION | Component: 10 ~ 500Hz, 2G 10min./1cycle, 60min. each along X, Y, Z axes; Mounting: Compliance to IEC60068-2-6 | ||||
SAFETY STANDARDS | UL508, TUV EN60950-1 approved | ||||
SAFETY & | WITHSTAND VOLTAGE | I/P-O/P: 3KVAC I/P-FG: 2KVAC O/P-FG: 0.5KVAC | |||
EMC | ISOLATION RESISTANCE | I/P-O/P, I/P-FG, O/P-FG:100M Ohms / 500VDC / 25C/ 70% RH | |||
EMC EMISSION | Compliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3 | ||||
EMC IMMUNITY | Compliance to EN61000-4-2, 3, 4, 5, 6, 8, 11, EN55024, EN61000-6-1, EN61204-3, light industry level, criteria A | ||||
MTBF | 236.9K hrs min. MIL-HDBK-217F (25C) | ||||
OTHERS | DIMENSION | 22.5*90*100mm (W*H*D) | |||
PACKING | 0.19Kg; 72pcs/14.7Kg/0.91CUFT | ||||
NOTE | 1.All parameters NOT specially mentioned are measured at 230VAC input, rated load and 25°C of ambient temperature. | ||||
2.Ripple & noise are measured at 20MHz of bandwidth by using a 12” twisted pair-wire terminated with a 0.1 uf & 47uf parallel capacitor. | |||||
3.Tolerance : includes set up tolerance, line regulation and load regulation. | |||||
4.The power supply is considered a component which will be installed into a final equipment. The final equipment must be re-confirmed that it still meets EMC directives. | |||||
5.Length of set up time is measured at cold first start. Turning ON/OFF the power supply may lead to increase of the set up time. |