• MDR-60
  • MDR-60

MDR-60

Description:

MDR-60 is a slim line DIN rail Class I switching power supply.Designed with a fully isolated plastic case to prevent user contact and the risk of shock.Featuring up to 88% efficiency this series can be cooled using only free air convection up to 60°C which significantly increases the reliability and lifetime of the power supply.Other standard features include its low no-load power consumption, to save energy, short circuit, overload, and over voltage protections, and DC OK relay contact with LED indicator for monitoring the PSU status.

Inquiry >

  • Type and Specification

     
     
Model     
     
     

MDR-60-5MDR-60-12MDR-60-24MDR-60-48
OutputDC Voltage5V12V24V48V
Rated Current10A5A2.5A1.25A
Current Range0 ~ 10A0 ~5A0 -2.5A0-1.25A
Rated Power50W60W60W60W
Ripple & Noise (max.)80mVp-p120mVp-p150mVp-p200mVp-p
Voltage ADJ Range5 -6V12-15V24 – 30V48 ~ 56V
Voltage Tolerance±2.0%±1.0%±1.0%±1.0%
Line Regulation±1.0%±1.0%±1.0%±1.0%
Load Regulation±1.5%±1.0%±1.0%±1.0%
Setup, Rise Time Note.5500ms, 30ms/230VAC
500ms, 30ms/115VAC
at full load
Hold Up Time (Typ.)50ms/230VAC
20ms/115VAC
at full load
InputVoltage Range85~264VAC
120~370VDC
Frequency Range47~63Hz
Efficiency (Typ.)78%86%88%87%
AC Current (Typ.)1.8A/115VAC
1A/230VAC
Inrush Current (Typ.)COLD START:
30A/115VAC
60A/230VAC
Leakage Current<1mA/240VAC
ProtectionOver-load105% ~ 150% rated output power
Protection type: Constant current limiting, recovers automatically after fault condition is removed
Over-voltage6.25-7.25V15.6 – 18V31.2-36V57.6 – 64.8V
Protection type: Shut down o/p voltage, re-power on to recover
FunctionDC SignalRelay contact rating (max.): 30V/1A resistive
EnvironmentWorking Humidity20% ~ 90%RH non-condensing
Storage Temp Humidity-40°C ~ +85°C, 10% ~ 95%RH
Temp Coefficient±0.03%/°C (0 – 50°C)
VibrationComponent: 10 – 500Hz, 2G 10min./1 cycle, the period for 60min. each along X, Y, and Z axes; Mounting: Compliance to IEC60068-2-6
Safety & EMCSafety StandardsUL508, UL60950-1, TUV EN60950-1 approved
Withstand Voltagel/P-0/P: 3KVAC
l/P-FG:2KVAC
0/P-FG: 0.5KVAC
Isolation Resistancel/P-O/P, l/P-FG, 0/P-FG:>100M Ohms/500VDC/25°C/70% RH
EMC EmissionCompliance to EN55011, EN55022 (CISPR22), EN61204-3 Class B, EN61000-3-2,-3
EMC ImmunityCompliance to EN6100(M-2, 3, 4, 5, 6, 8,11, EN55024, EN61000-6-2, EN61204-3, heavy industry level, criteria A
OthersMTBF299.2K hrs min. MIL-HDBK-217F (25°C)
Dimension40*90*100mm (W*H*D)
Packing0.33Kg; 60pcs/20Kg/0.82CUFT
Note1. All parameters NOT specially mentioned are measured at 230VAC input, rated load, and 25°C of ambient temperature.
2. Ripple & noise are measured at 20MHz of bandwidth by using a 12″ twisted pair-wire terminated with a 0.1 of & 47uf parallel capacitor.
3. Tolerance: includes set up tolerance, line regulation, and load regulation.
4. The power supply is considered a component that will be installed into the final equipment. The final equipment must be re-confirmed that it still meets EMC directives. For guidance on how to perform these EMC tests, please refer to “EMI testing of component power supplies.
5. The length of set-up time is measured at the first cold start. Turning ON/OFF the power supply may lead to an increase in the setup time.